AirSenseTM
 
line decor
  
Contact Us

 

 
line decor
 
   
 

Digital Control Systems

7401 SW Capitol Hwy. Portland, OR. 97219 USA

Toll Free: 1-877-468-6337

Phone: (503)246-8110

Fax: (503) 246-6747 


 

AirSense Model 301A

PDF manual Model 301A Manual

TRANSFORMERS ARE AVAILABLE FOR EITHER 110 OR 220 VOLT OPERATION

Housed in a sleek ( 2.5 by 4.5 inches) case, our new generation Model 301A is the first choice for building ventilation system professionals. With an unprecedented 2 year warranty and only one gas required for calibration (rather than zero and a calibration gas mix) the 301A is the user-friendly CO2 monitor everyone wants.

    The 301A is the cutting edge of infrared technology: excellent long-term drift performance is enhanced by a stable IR source, a state-of-the-art lithium tantalate detector, updated digital electronics and unique auto-zero function. This results in very stable calibration and longer trouble-free operation in the field. The new IR source is more rugged, operates at 10X derated power and has a life expectancy of at least 10 years.   The  lithium tantalate detector enhances stability, has less ambient temperature sensitivity, and faster response time.

    Each unit is electronically isolated so that multiple units can be connected to the same controller without electrical interference.

    The Model 301A is extremely versatile, with digital display, and 120VAC power supply option available. The unit has both voltage and 4-20mA outputs. Its new smaller size with power consumption as low as 60mA and 0.8W make it ideal for battery-operated portable applications.

 

 

m301A duct.jpg (18346 bytes)Manuals

Model 301A Manual 2000ppm

M301A 5000 ppm (spline)

 

 

Specification

Operating Principal

Non-dispersive Infrared (NDIR)

Gas Sampling Method

Diffusion

Measurement Range

0-2000 ppm CO2 (optional up to 0-5000 available)

Maximum Annual Drift

+/- 75 ppm

Accuracy

+/- 5% of reading or 75 ppm: whichever is greater

Repeatability

+/- 20 ppm

Minimum Calibration Interval

Two years

Response Time

Less than one minute

Operating Temperature Range

10-50°C

Power Requirements

18-30VDC or 20-30V RMS AC

Power Consumption

Less then 1W

Calibration Adjustments

Span only (offset electronically nulled)

Case Dimensions

4.9" x 2.6" x 1.6"

Enclosure Material

High impact plastic

Voltage Output (linear)

0-10VDC standard (other ranges available)

Optional Digital Display

4 Digit, .3" 7-segment LED (available in red or green)

Operating Life Expectancy

10 Years minimum

Warranty

2 years, parts and labor through repair or exchange

 
 

 

Indoor Air Quality: