Digital Control Systems' AirSense™ Model 307 Carbon Dioxide Sensor sets a new standard of affordability and user-friendly installation and operation. A uniquely-plated CO2 sensing cell ensures flawless performance in the most demanding HVAC environment. The Model 307's ease of installation and classic finish were designed to meet the needs of the cost-conscious HVAC contractor.
The AirSense™ M307 was designed to be installed on a standard electrical junction box in new construction projects, or it can be directly wall mounted. Installation is now easier than ever! The Model 307 can be installed with just two screws and none of the sensitive electronics are exposed during installation, eliminating costly accidents. Another unique feature of the Model 307 is that it is designed so that components will not be harmed if the unit is accidentally wired incorrectly.
Technicians in the field can now easily calibrate the AirSense™ Model 307 using a simple one-step calibration procedure (patent pending): simply remove the port cap, attached the 2000 ppm calibration gas (available from the factory),
and press a single button. A green LED indicates that the
calibration process is complete.
The AirSense™ Model 307 provides ease of installation, built-in circuit protection, versatility, and the only one-point calibration system (patent pending) on the market. All of these cost-saving features are supplemented by a sleek design and flexible configurations, including and optional 4-20mA current loop module.
Measurement output is via a 0 to 10V interface.
Specifications
|
Operating Principle
|
Non-dispersive infrared (NDIR)
|
Gas Sampling Method
|
Diffusion Only
|
Measurement Range
|
0-2000 ppm Standard (0-5000ppm Range Optional by Request)
|
Repeatability
|
± 20 ppm
|
Measurement Accuracy
|
± 5% of reading or 75 ppm,
(whichever is greater)
|
Recommended Calibration Interval
|
5 years
|
Warm Up Time
|
Less than 1 minute
|
Power Requirements
|
18 - 30 VDC or 20 - 28 VRMS AC
|
Power Consumption
|
Less than 1 watt
|
Operating Temperature Range
|
0 - 50° Celsius
|
Operating Humidity Range
|
5 - 95% RH, non-condensing
|
Voltage Output (linear)
|
0 - 10 VDC full scale
|
Optional Current Output (linear)
|
|
Calibration
|
4-20 mA (Rloop : 400 ohms maximum)
Single button
|
Case Dimensions
|
4.5 x 2.8 x 0.9 inches
|
Enclosure Material
|
White Satin Finish, ABS UL 94 V-O
Flammablility Rated Plastic
|
|